| 2015-08-05 08:38:50 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15071004 | | | 8/5/15 | | | | | | 1) SHEET M-1: THE OUTSIDE AIR CALCULATION SCHEDULE IS | | | REFERENCING THE OUTDATED ASHRAE 62.1- 2004. PLEASE | | | REVIEW AND REVISE THE CALCULATIONS IN COMPLIANCE WITH | | | SECTION 809.2 FBC-14 EXISTING BUILDING CODE: ALTERED | | | EXISTING SYSTEMS. | | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | | PROCEDURE OF ASHRAE 62. | | | 2) M-2: THE AIR DISTRIBUTION TAG PRINT AT THE DIFFUSERS | | | IS TOO SMALL TO READ. PLEASE ENLARGE EITHER THE TAGS OR | | | THE ENTIRE DRAWING TO EXPEDITE THE REVIEW- SECTION | | | 107.2.1 WPB AMENDEMENTS TO THE FBC-14 BUILDING CODE. | | | 3) M-2: LABEL (VAV 6-7) ON THE PLAN AS "NEW" | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|