| Plan Review Notes For Permit 15071002 |
| Permit Number |
15071002 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-11 13:18:49 | 1451 SOUTH OLIVE AVENUE | | | PERMIT #15071002 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | OCCUPANCY OF THE CONSTRUCTION TRAILERS IS NOT PERMITTED | | | UNTIL A #131 FIRE FINAL INSPECTION HAS BEEN PASSED. | | | | | | A SEPARATE PERMIT IS NEEDED FOR INSTALLING AUTOMATIC | | | FIRE SPRINKLERS. | | | | | | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING | | | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE | | | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN | | | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE | | | BACKGROUND. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|