| 2016-08-24 16:16:17 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 354 MARLBORO PL. REAR |
| | DESCRIPTION: INTERIOR RENOVATIONS OF REAR BLDG. |
| | MASTER PERMIT: 15070952 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. CORRECT THE TITLE BLOCK TO INCLUDE THE ELECTRICAL |
| | WORK. ACCORDING TO THE EXISTING TITLE BLOCK, NO |
| | ELECTRICAL WORK IS TO BE DONE. |
| | 2. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE FPL |
| | UTILITY POLE AND SERVICE DROP TO THE METER. INCLUDE THE |
| | MAIN SERVICE DISCONNECT. |
| | 3. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS |
| | ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED. |
| | THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND |
| | INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE |
| | SPECIFIC. |
| | 4. FBC-RE E3705.8/NEC240.24(B): READY ACCESS FOR |
| | OCCUPANTS. EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL |
| | OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING |
| | THAT OCCUPANCY. THE SUBMITTED DRAWINGS SHOW THE |
| | ELECTRICAL PANEL IN THE GARAGE WITH NO DIRECT ACCESS TO |
| | THE UPPER BLDG. |
| | 5. FBC-RE 3903.3/NEC 210.70: ILLUMINATION FOR THE |
| | STAIRWAY IS REQUIRED. FURTHERMORE, THE STAIRWAY |
| | LIGHTING SHALL BE CONTROLLED FROM BOTH TOP AND BOTTOM |
| | UNLESS AUTOMATIC CONTROL IS INSTALLED. |
| | 6. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A |
| | PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING |
| | THE SPECIFIC PURPOSE OF EVERY CIRCUIT. |
| | 7. E3601.6.2: SERVICE DISCONNECT LOCATION. THE SERVICE |
| | DISCONNECTING MEANS SHALL BE INSTALLED AT A READILY |
| | ACCESSIBLE LOCATION EITHER OUTSIDE OF A BUILDING OR |
| | INSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE |
| | CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL NOT BE |
| | INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE ACCESS |
| | TO THE DISCONNECT SERVING THE DWELLING UNIT IN WHICH |
| | THEY RESIDE. INDICATE IF THE PANEL IS MAIN LUG ONLY OR |
| | MAIN BREAKER. |
| | 8. R404.1: LIGHTING EQUIPMENT (MANDATORY). A MINIMUM OF |
| | 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| | MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY |
| | LAMPS. |
| | 9. R303.9: REQUIRED HEATING. WHEN THE WINTER DESIGN |
| | TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C), |
| | EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING |
| | FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM |
| | TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM) |
| | ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS |
| | IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE |
| | INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS |
| | SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS |
| | SECTION. THEREFORE HEAT SHALL BE PROVIDED FOR FINAL |
| | INSPECTION. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |