| 2016-04-06 17:49:43 | RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW |
| | CHECKLIST. (REAR BUILDING). |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | *****NOTE: ACCORDING TO FLORIDA STATUTE 553.80(2)(B) |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE EACH TIME AFTER THE THIRD REVIEW. |
| | |
| | |
| | 1- PLANS SHOW NEW OPENINGS FOR GARAGE OVERHEAD DOORS. |
| | PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR |
| | THE NEW GARAGE DOORS. SPECIFY REINFORCEMENT AT THE ENDS |
| | OF EACH OPENING. SPECIFY LINTEL OR BEAM, SPECIFY |
| | STRUCTURAL BUCK ATTACHMENT, ETC. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | RESPONSE: A) DETAIL SUBMITTED DOESN'T PROVIDE ANY |
| | STRUCTURAL SPECIFICATIONS FOR THE REINFORCEMENT AT THE |
| | ENDS OF EACH OPENING. THERE ARE NO SPECIFICATIONS |
| | SHOWING HOW THE EXISTING MASONRY WALLS ARE REINFORCED |
| | TO RECEIVE THE LOADS OF THE NEW GARAGE DOORS. |
| | |
| | B) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 1/2 |
| | ANCHOR BOLTS SPECIFIED ON THE GARAGE DOOR BUCK DETAIL. |
| | SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | NOTE: ONLY THE FRONT BUILDING IS CONTRIBUTING HISTORIC |
| | BUILDING. THE REAR BUILDING IS NOT. THEREFORE, IT'S NOT |
| | EXEMPT FROM THE ENERGY CODE. |
| | |
| | RESPONSE: RESPONSE LETTER STATES "A/C & HEAT UNDER |
| | SEPARATE PERMIT W/ ENERGY CALCULATIONS". THIS DOESN'T |
| | ADDRESS THE COMMENT. ENERGY CALCULATIONS AND A/C & HEAT |
| | CALCULATIONS ARE TWO DIFFERENT THINGS. THE INFORMATION |
| | FOR THE A/C & HEAT CALCULATIONS ALONG WITH THE A/C |
| | PLANS MAY BE SUBMITTED UNDER A SEPARATE PERMIT BUT THE |
| | ENERGY CALCULATIONS NEED TO BE SUBMITTED NOW. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | DWELLING/GARAGE FIRE SEPARATION AS REQUIRED BY SEC. |
| | R302.6 OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | RESPONSE: SPECIFICATIONS ON PLANS DOESN'T SPECIFY THE |
| | TYPE OF GYPSUM WALL BOARD AS REQUIRED BY TABLE R302.6 |
| | OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | ****ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| | ADDRESSING EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |