| 2016-02-16 16:43:56 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW |
| | CHECKLIST. (REAR BUILDING). |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | NOTE: |
| | PLANS WERE REVISED. NEW SCOPE OF WORK IS SHOWN. |
| | COMMENTS BELOW ARE BASED ON THE NEW PLANS PROVIDED. |
| | |
| | 1- VALUATION DECLARED IN THE PERMIT APPLICATION. REVISE |
| | VALUATION TO INCLUDE ALL THE SCOPE OF WORK SHOWN ON |
| | PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. |
| | |
| | 2- PLANS SHOW NEW OPENINGS FOR GARAGE OVERHEAD DOORS. |
| | PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR |
| | THE NEW GARAGE DOORS. SPECIFY REINFORCEMENT AT THE ENDS |
| | OF EACH OPENING. SPECIFY LINTEL OR BEAM, SPECIFY |
| | STRUCTURAL BUCK ATTACHMENT, ETC. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 3- ACCORDING TO NEW PLANS PROVIDED, THIS IS ALTERATION |
| | LEVEL 3 NOT ALTERATION LEVEL 2. REVISE DESIGN CRITERIA |
| | INFORMATION AS REQUIRED. SEC. 505 OF FBC-EXISTING |
| | BUILDING, 5TH EDITION (2014). |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | NOTE: ONLY THE FRONT BUILDING IS CONTRIBUTING HISTORIC |
| | BUILDING. THE REAR BUILDING IS NOT. THEREFORE, IT'S NOT |
| | EXEMPT FROM THE ENERGY CODE. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR THE INSWING DOOR SHOWN ON THE |
| | FIRST FLOOR PLAN. |
| | |
| | 6- ENGINEER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | DWELLING/GARAGE FIRE SEPARATION AS REQUIRED BY SEC. |
| | R302.6 OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 8- PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE |
| | HEATING REQUIREMENTS OF SEC. R303.9 OF FBC RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | |
| | 9- SHOW CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | SLEEPING ROOMS AS REQUIRED BY SEC. R315.1. NOTE: THERE |
| | IS A NEW GARAGE BELOW THE DWELLING UNIT. |
| | |
| | ****ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| | ADDRESSING EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |