| Plan Review Notes For Permit 15070942 |
| Permit Number |
15070942 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-10-21 12:26:00 | 1) THE WATER RISER DIAGRAM ON SHT.P-2 SHALL SHOW ALL | | | THE WATER PIPING TO ALL THE FIXTURES SHOWN ON SHT.P-3 | | | AND INCLUDE ALL THE PIPE SIZES, BOTH FILTRATION | | | SYSTEMS, ETC. WPB AMEND. TO FBC SEC. 107.2.1. | | | CLARIFY WHY THERE ARE TWO WATER RISER DIAGRAMS, ONE ON | | | P-2 AND ONE ON P-3 AND NEITHER ONE MATCHES THE OTHER. | | | SUBMIT ONE WATER RISER DIAGRAM SHOWING ALL THE | | | FIXTURES/APPLIANCES CONNECTED THERETO OR SUPPLY BOTH | | | WATER RISERS THAT CORRELATE. | | | 2) YOU HAVE SUBMITTED GREASE TRAP SIZING CALCULATIONS | | | BASED ON 4 SEATS. WHERE ARE THE FOUR SEATS COMING FROM | | | WHEN THERE ARE NO SEATS SHOWN ON THE PLANS? CLARIFY. | | | | | | PLEASE CALL ME TO DISCUSS THESE COMMENTS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|