| Plan Review Notes For Permit 15070942 |
| Permit Number |
15070942 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-10-21 07:02:25 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15070942 | | | 10/21/15 | | | | | | 1) M-1: THE REVISED AIR BALANCE SCHEDULE INDICATES A | | | DEFICIENT AMOUNT OF O/A CFM'S FOR OCCUPANTS BASED ON | | | THE REVISED O/A CALCULATIONS AND TABLE 403.3 FBC-14 | | | MECHANICAL- 675 CFM REQUIRED/550 PROVIDED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|