Plan Review Notes For Permit 15070942
Permit Number 15070942
Review Stop P
Sequence Number 2
Notes
Date Text
2015-10-02 14:08:451) THE WATER RISER DIAGRAM ON SHT.P-2 SHALL SHOW ALL
 THE WATER PIPING TO ALL THE FIXTURES SHOWN ON SHT.P-3
 AND INCLUDE ALL THE PIPE SIZES, BOOSTER PUMP, BOTH
 FILTRATION SYSTEMS, ETC. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SUBMIT SIZING CALCULATIONS TO ENSURE THAT THE
 EXISTING TANK HAS THE CAPACITY TO HANDLE THE ADDITIONAL
 GREASE WASTE. WPB AMEND. TO FBC SEC. 107.2.1., 2014
 FBC-PLUMBING SEC.1003.2. 2ND REQUEST.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR