| Plan Review Notes For Permit 15070942 |
| Permit Number |
15070942 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-06 14:27:44 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15070942 | | | 10/6/15 | | | | | | 1) M-1: THE OUTSIDE AIR CALCULATIONS ARE NOT IN | | | COMPLIANCE WITH ASHRAE 62.1 OR TABLE 403.3 FBC-14 | | | MECHANICAL. EACH TABLE REQUIRES A RATE OF 7.5 CFM PER | | | OCCUPANT PLUS 0.18 CFM PER SQ. FT FOR CAFETERIA/FAST | | | FOOD. PLEASE REVISE THE CALCULATIONS. | | | 2) M-1: THE AIR BALANCE SCHEDULE MUST INDICATE HOW MUCH | | | OF THE O/A IS BEING PROVIDED FOR OCCUPANTS AND HOW MUCH | | | FOR MAKE-UP AIR FOR THE EXHAUST SYSTEMS. PLEASE NOTE | | | THAT MAKE UP AIR CFM'S SHALL BE APPROXIMATELLY EQUAL TO | | | REQUIRED EXHAUST CFM'S- SECTION 508.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|