Plan Review Notes
Plan Review Notes For Permit 15070942
Permit Number 15070942
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-08 04:58:451) INDICATE THE SIZE OF THE EXISTING GREASE TRAP AND
 SUBMIT SIZING CALCULATIONS TO ENSURE THAT THE EXISTING
 TANK HAS THE CAPACITY TO HANDLE THE ADDITIONAL GREASE
 WASTE. WPB AMEND. TO FBC SEC. 107.2.1., 2014
 FBC-PLUMBING SEC.1003.2.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 NE W EQUIPMENT USED FOR FOOD PREP/BEVERAGES/ICE CREAM,
 ETC. EQUIPMENT SHALL COMPLY WITH NSF.
 3) SHEETS K-1, K-2, K-3 APPEAR TO HAVE THE COLUMN
 HEADING MISSING. CLARIFY.
 4) SUBMIT A DETAIL FOR THE NEW GREASE WASTE CONNECTION
 TO THE EXISTIN GREASE INTERCEPTOR. COMPLY WITH FL.
 ADMIN. CODE RULE 64E-6 FOR REQUIREMENTS.
 5) THE WATER PIPE SIZES ON THE PIPNG DIAGRAM ON P-3 DO
 NOT CORRELATE WITH THE SIZES ON THE WATER RISER ON P-2.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  