| 2015-08-18 09:55:27 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15070942 |
| | 8/18/15 |
| | |
| | 1) REFER TO THE FBC-14 EXISITNG BUILDING CODE. PLEASE |
| | ADD THE CODE TO THE DESIGN CODES LIST ON SHEET CS-1 AND |
| | SEE SECTION 809.2- ALTERED EXISTING SYSTEMS. |
| | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL |
| | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR |
| | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER |
| | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR |
| | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION |
| | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF |
| | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY |
| | PROCEDURE OF ASHRAE 62.1. PLEASE PROVIDE AN OUTSIDE AIR |
| | CALCULATION AND SCHEDULE ON THE PLAN INDICATING THE |
| | REQUIRED O/A AND THE O/A PROVIDED. |
| | 2) THE CITY OF WEST PALM BEACH DEVELOPMENT SERVICES |
| | DEPARTMENT REQUIRES A SEPARATE PERMIT FOR ALL KITCHEN |
| | HOOD INSTALLATIONS. PLEASE PLACE A NOTE ON THE PLANS |
| | ACCORDINGLY. |
| | IN REFERENCE TO THIS PERMIT SET OF PLANS IT IS |
| | NECESSARY TO INDICATE HOW MAKE-UP AIR IS BEING PROVIDED |
| | FOR THE NEW EXHAUST HOOD TO VERIFY PROPER AIR BALANCING |
| | WITHIN THE ALTERED SPACE- REFER TO SECTION 508 FBC-14 |
| | MECHANICAL. |
| | 508.1 MAKEUP AIR. |
| | MAKEUP AIR SHALL BE SUPPLIED DURING THE OPERATION OF |
| | COMMERCIAL KITCHEN EXHAUST SYSTEMS THAT ARE PROVIDED |
| | FOR COMMERCIAL COOKING APPLIANCES. THE AMOUNT OF MAKEUP |
| | AIR SUPPLIED TO THE BUILDING FROM ALL SOURCES SHALL BE |
| | APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AIR FOR |
| | ALL EXHAUST SYSTEMS FOR THE BUILDING. THE MAKEUP AIR |
| | SHALL NOT REDUCE THE EFFECTIVENESS OF THE EXHAUST |
| | SYSTEM. MAKEUP AIR SHALL BE PROVIDED BY GRAVITY OR |
| | MECHANICAL MEANS OR BOTH. MECHANICAL MAKEUP AIR SYSTEMS |
| | SHALL BE AUTOMATICALLY CONTROLLED TO START AND OPERATE |
| | SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. MAKEUP AIR |
| | INTAKE OPENING LOCATIONS SHALL COMPLY WITH SECTION |
| | 401.4. |
| | 508.1.1 MAKEUP AIR TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | PLEASE REVISE THE PLANS TO SHOW COMPLIANCE WITH THE |
| | CODE SECTIONS ABOVE. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |