| 2015-08-25 16:07:46 | 1ST REVIEW: FBC 2014 5TH ED. |
| | |
| | FROM CITY RECORDS, IT CANNOT BE ASCERTAINED THAT THE |
| | AREA DEPICTED ON THE PLAN SHOWN AS "AS BUILT" AND |
| | INDICATED AS HABITAL SPACE CONSISTING OF A FAMILY ROOM, |
| | TWO BEDROOMS, A LIVING ROOM AND LAUNDRY ROOM, WAS |
| | PREVIOUSLY CONSTRUCTED FOR HABITAL USE WITHIN THE R3 |
| | OCCUPANCY CLASSIFICATION. PERMIT 6365I WAS ISSUED ON |
| | 6/1/1983, I PRESUME THAT IS WHEN THE APPROXIMATELY 650 |
| | SF AREA WAS BUILT. THE PROPERTY APPRAISER WEB SITE |
| | SHOWS THIS PORTION OF THE STRUCTURE AS "SEMI FINISHED |
| | BASE AREA." |
| | |
| | PLEASE PROVIDE ANY RECORDS YOU MAY HAVE TO DEMONSTRATE |
| | CONSTRUCTION DETAILS OF THIS PART OF THE STRUCTURE. |
| | ALTERNATIEVLY, IF THE IMPROVEMENTS ARE AS COMPLETE AS |
| | THE PLAN INDICATES, PROVIDE THE FOLLOWING: |
| | |
| | AN ENERGY SUBMITTAL |
| | |
| | FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | DETAILS TO DEMONSTRATE PROPOSED OR EXISTING BUILDING |
| | ENVELOPE THERMAL EFFICIENTCY. |
| | |
| | FBC - R301.2.1.2 PROTECTION OF OPENINGS. PROVIDE AN |
| | IMPACT PROTECTION SUBMITTAL. |
| | WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS |
| | REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM |
| | WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR |
| | WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12 |
| | OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN. |
| | |
| | ADVISORY COMMENT IF WORK WAS COMPLETED WITHOUT A PERMIT |
| | PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY |
| | COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR |
| | INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL |
| | CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 |
| | & FBC 117. |
| | |
| | FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A |
| | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| | PURPOSES UNTIL APPROVED. |
| | |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |