| 2015-08-04 10:48:55 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. YOUR NARRATIVE WHICH IS PART OF THE SUBMITTAL | | | EXCLUDES THE ADDITION OF NOTES 59 & 60 ON PAGE E0.1 | | | 2. THE LIGHTING FIXTURE SCHEDULE ON PAGE E1.1 DOES NOT | | | INCLUDE A TYPE M FIXTURE DESCRIPTION MAKING IT | | | IMPOSSIBLE TO VERIFY CONFORMANCE WITH FBC-E SECTION | | | 505.5.3. | | | 3. THE VARIOUS ROOM DESIGNATIONS ARE ILLEGIBLE MAKING | | | IT DIFFICULT TO CONFIRM THE CHANGES MENTIONED. | | | 4. PAGE E1.1 HAS ADDITIONAL CHANGES NOT ADDRESSED ON | | | THE NARRATIVE. | | | 5. PROVIDE A LIGHTING POWER DENSITY CHART FOR THE AREA | | | COMPLIANT WITH FBC-ENERGY CONSERVATION TABLE 505.5.3. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|