2015-08-04 10:48:55PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOUR NARRATIVE WHICH IS PART OF THE SUBMITTAL
 EXCLUDES THE ADDITION OF NOTES 59 & 60 ON PAGE E0.1
 2. THE LIGHTING FIXTURE SCHEDULE ON PAGE E1.1 DOES NOT
 INCLUDE A TYPE M FIXTURE DESCRIPTION MAKING IT
 IMPOSSIBLE TO VERIFY CONFORMANCE WITH FBC-E SECTION
 505.5.3.
 3. THE VARIOUS ROOM DESIGNATIONS ARE ILLEGIBLE MAKING
 IT DIFFICULT TO CONFIRM THE CHANGES MENTIONED.
 4. PAGE E1.1 HAS ADDITIONAL CHANGES NOT ADDRESSED ON
 THE NARRATIVE.
 5. PROVIDE A LIGHTING POWER DENSITY CHART FOR THE AREA
 COMPLIANT WITH FBC-ENERGY CONSERVATION TABLE 505.5.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  