Plan Review Notes
Plan Review Notes For Permit 15070747
Permit Number 15070747
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-01 08:40:452ND REVIEW: FBC 2014 5TH ED.
  
 COMMENTS FROM 1ST REVIEW:
 1) REVISE THE CODE REFERENCE CITED ON SHEET FP AS IT IS
 INCORRECT. THE APPLICABLE CODE IS THE FBC 5TH EDITION
 EXISTING BUILDING VOLUME.
 COMPLIED
  
 2) PLEASE NOTE THE WINDOWS HAVE BEEN PERMITTED UNDER
 SEPARATE PERMIT. NO ADDITIONAL REVIEW FOR WINDOWS WILL
 BE CONDUCTED.
 N/A
  
 3) PROVIDE MORE INFORMATION OR MANUFACTURER?S
 INFORMATION ON THE CAST STONE FIREPLACE. WILL IT BE
 INCORPORATED INTO THE CHIMNEY TO REMAIN? IF SO, PROVIDE
 DETAIL REVIEWED BY THE ARCHITECT CONSISTENT WITH THE
 MANUFACTURER?S INSTALLATION REQUIREMENTS.
 COMPLIED, PLANS NOTED AS DECORATIVE ONLY, FAUX, NON
 WORKING FIRE PLACE
  
 4) AS FOR THE CHIMNEY, NOTES ARE PROVIDED IN THE
 CHIMNEY SUPPORT DETAIL AS FOLLOWS: #6 DOWELS @ 4" O.C.;
 4" X6"X .25 "X 3.5' L; I DO NOT UNDERSTAND WHAT THIS IS
 AND IF IT IS INTENDED TO SUPPORT THE CHIMNEY OR IF IT
 IS AN ELEVATED SLAB W/ UNEQUAL ANGLES CHIMNEY? IF STEEL
 ANGLES, IS THERE A WELD?
 PROVISIONALLY APPROVED. THE ARCHITECT HAS PROVIDED A
 CERTIFICATION FOR THIS WORK AS COMPLETED AND CHANGED
 THE DETAIL, HOWEVER, THE WORK DEPICTED ON THE PLAN IS
 UNCLEAR AND WILL BE SUBJECT TO ACCEPTANCE BY THE FIELD
 INSPECTOR.
  
 5) PROVIDE DETAIL, PERHAPS BY THE STEEL FABRICATOR, AND
 REVIEWED BY THE ARCHITECT AS TO ALL STEEL CONNECTIONS
 SUCH AS COLUMN TO FLOOR, COLUMN TO BEAM, BEAM TO BEAM,
 & BEAM TO CONCRETE BEAM/BEARING PLATES.
 PROVISIONALLY APPROVED. THE ARCHITECT HAS PROVIDED A
 CERTIFICATION FOR THIS WORK AS COMPLETED HOWEVER, SOME
 CONNECTION DETAILS ARE STILL MISSING, AND WILL BE
 SUBJECT TO ACCEPTANCE BY THE FIELD INSPECTOR.
  
 6) THERE IS A SINGLE 2X4 TOP PLATE OVER A STEEL BEAM TO
 BE CONNECTED BY STAGGERED THROUGH BOLTS. WILL THIS
 ALLOW FOR 5/8" EDGE DISTANCE CONSISTENT WITH FBCR602 ?
 PROVIDE A DETAIL.
 PROVISIONALLY APPROVED, SUBJECT TO ACCEPTANCE BY THE
 FIELD INSPECTOR.
 .
 7) THE SINGLE TOP PLATE IS PROPOSED TO BE CONNECTED TO
 EXISTING ROOF FRAMING MEMBERS WITH A SIMPSON H10. THIS
 CONNECTOR IS DESIGNED FOR CONNECTION TO A DOUBLE, NOT A
 SINGLE TOP PLATE. PROVIDE AN ALTERNATE CONNECTOR.
 COMPLIED
  
 8) PROVIDE AN ATTACHMENT SCHEDULE FOR THE DENS GLASS TO
 THE WOOD FRAMING. PROVIDE ADDITIONAL FRAMING DETAILS
 FOR STUDS TO TOP & BOTTOM PLATES AND SPECIFY
 CONNECTORS. PROVIDE THE THICKNESS OF STUCCO.
 COMPLIED
  
 AN ENERGY SUBMITTAL MAY BE REQUIRED UNLESS THE
 STRUCTURE IS EXEMPT PER FBCE 101.4.2, HISTORIC
 BUILDINGS
 HISTORIC, EXEMPT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710