| Date |
Text |
| 2015-08-18 14:06:21 | 1ST REVIEW: FBC 2014 5TH ED. |
| | |
| | REVISE THE CODE REFERENCE CITED ON SHEET FP AS IT IS |
| | INCORRECT. THE APPLICABLE CODE IS THE FBC 5TH EDITION |
| | EXISTING BUILDING VOLUME. |
| | |
| | PLEASE NOTE THE WINDOWS HAVE BEEN PERMITTED UNDER |
| | SEPARATE PERMIT. NO ADDITIONAL REVIEW FOR WINDOWS WILL |
| | BE CONDUCTED. |
| | |
| | PROVIDE MORE INFORMATION OR MANUFACTURER?S INFORMATION |
| | ON THE CAST STONE FIREPLACE. WILL IT BE INCORPORATED |
| | INTO THE CHIMNEY TO REMAIN? IF SO, PROVIDE DETAIL |
| | REVIEWED BY THE ARCHITECT CONSISTENT WITH THE |
| | MANUFACTURER?S INSTALLATION REQUIREMENTS. |
| | |
| | AS FOR THE CHIMNEY, NOTES ARE PROVIDED IN THE CHIMNEY |
| | SUPPORT DETAIL AS FOLLOWS: #6 DOWELS @ 4" O.C.; 4" X6"X |
| | .25 "X 3.5' L; I DO NOT UNDERSTAND WHAT THIS IS AND IF |
| | IT IS INTENDED TO SUPPORT THE CHIMNEY OR IF IT IS AN |
| | ELEVATED SLAB W/ UNEQUAL ANGLES CHIMNEY? IF STEEL |
| | ANGLES, IS THERE A WELD? |
| | |
| | PROVIDE DETAIL, PERHAPS BY THE STEEL FABRICATOR, AND |
| | REVIEWED BY THE ARCHITECT AS TO ALL STEEL CONNECTIONS |
| | SUCH AS COLUMN TO FLOOR, COLUMN TO BEAM, BEAM TO BEAM, |
| | & BEAM TO CONCRETE BEAM/BEARING PLATES. |
| | |
| | THERE IS A SINGLE 2X4 TOP PLATE OVER A STEEL BEAM TO BE |
| | CONNECTED BY STAGGERED THROUGH BOLTS. WILL THIS ALLOW |
| | FOR 5/8" EDGE DISTANCE CONSISTENT WITH FBCR602 ? |
| | PROVIDE A DETAIL. THE SINGLE TOP PLATE IS PROPOSED TO |
| | BE CONNECTED TO EXISTING ROOF FRAMING MEMBERS WITH A |
| | SIMPSON H10. THIS CONNECTOR IS DESIGNED FOR CONNECTION |
| | TO A DOUBLE, NOT A SINGLE TOP PLATE. PROVIDE AN |
| | ALTERNATE CONNECTOR. |
| | |
| | PROVIDE AN ATTACHMENT SCHEDULE FOR THE DENS GLASS TO |
| | THE WOOD FRAMING. PROVIDE ADDITIONAL FRAMING DETAILS |
| | FOR STUDS TO TOP & BOTTOM PLATES AND SPECIFY |
| | CONNECTORS. PROVIDE THE THICKNESS OF STUCCO. |
| | |
| | BASED ON THE FORGOING COMMENTS, A FULL REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME. ADDITIONAL COMENTS MAY ARISE |
| | UPON SECOND REVIEW. |
| | |
| | AN ENERGY SUBMITTAL MAY BE REQUIRED UNLESS THE |
| | STRUCTURE IS EXEMPT PER FBCE 101.4.2, HISTORIC |
| | BUILDINGS |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |