Plan Review Notes
Plan Review Notes For Permit 15070735
Permit Number 15070735
Review Stop B
Sequence Number 2
Notes
Date Text
2015-08-20 11:26:382ND REVIEW: FBC 2014 5TH ED.
  
 PROVIDE THE FOLLOWING AS A SUBMITTAL PRIOR TO
 INSTALLATION OF THE SKY PANELS TO THE SIGN STRUCTURE:
  
 ADDITIONAL DETAIL REGARDING THE ASSEMBLY AND WIND
 RESISTANCE CAPABILITY OF THE SKY PANEL SIGN. PER
 SECTION 6.0 CRITICAL FEATURES ON PAGE 17 OF 33 OF THE
 LISTING INFORMATION PROVIDED THE FIELD ASSEMBLY OF THIS
 SECTIONAL SIGN IS SUBJECT TO THE ACCEPTANCE OF THE
 LOCAL INSPECTION AUTHORITY.
  
 PROVIDE THE MANUFACTURERS INSTALLATION AND ASSEMBLY
 INSTRUCTIONS, PLEASE PROVIDE EVIDENCE THAT THE ENGINEER
 OF RECORD, CHRISTOPHER B. LAFORTE, P.E. HAS REVIEWED
 THE ASSEMBLY AND INSTALLATION INSTRUCTIONS FOR
 CONSISTENCY WITH HIS DESIGN AND THE THE SIGN PANEL HAS
 ADEQUATE WIND RESISTANCE CAPABILITY ITSELF.
  
 ADVISORY COMMENT:
  
 UPON INSTALLATION, A THIRD PARTY SHALL CERTIFY ALL
 BOLTED CONNECTIONS DEPICTED IN THE PLAN.
  
 A SEPARATE PERMIT IS REQUIRED FOR PLUMBING LINE
 RELOCATE AND FOR FLAG POLES RELOCATE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved