| Plan Review Notes For Permit 15070735 |
| Permit Number |
15070735 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-29 13:14:11 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. YOU SHALL PROVIDE A COMPLETE RISER DIAGRAM | | | INDICATING THE LOCATION OF THE POWER SOURCE. | | | 2. YOU SHALL INDICATE A PANEL SCHEDULE FOR THE SOURCE | | | POWER. | | | 3. REGARDLESS OF WHAT IT IS USED FOR, THIS IS | | | CONSIDERED A SIGN AND SHALL COMPLY WITH ALL THE | | | REQUIREMENTS OF ARTICLE 600 OF THE 2011 EDITION OF THE | | | NEC. | | | 4. ON THE SITE PLAN INDICATE THE LOCATION OF BOTH THE | | | SOURCE OF POWER AN WELL AS THE SIGN. AND THE WIRING | | | METHOD TO GET FROM POINT A TO B. | | | 5. IN ADDITION TO THE REQUIREMENTS OF THE NEC, | | | FBC-ENERGY CONSERVATION HAS SPECIFIC REQUIREMENTS WHICH | | | SHALL BE MET AS WELL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|