Plan Review Notes
Plan Review Notes For Permit 15070735
Permit Number 15070735
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-29 13:14:11PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SHALL PROVIDE A COMPLETE RISER DIAGRAM
 INDICATING THE LOCATION OF THE POWER SOURCE.
 2. YOU SHALL INDICATE A PANEL SCHEDULE FOR THE SOURCE
 POWER.
 3. REGARDLESS OF WHAT IT IS USED FOR, THIS IS
 CONSIDERED A SIGN AND SHALL COMPLY WITH ALL THE
 REQUIREMENTS OF ARTICLE 600 OF THE 2011 EDITION OF THE
 NEC.
 4. ON THE SITE PLAN INDICATE THE LOCATION OF BOTH THE
 SOURCE OF POWER AN WELL AS THE SIGN. AND THE WIRING
 METHOD TO GET FROM POINT A TO B.
 5. IN ADDITION TO THE REQUIREMENTS OF THE NEC,
 FBC-ENERGY CONSERVATION HAS SPECIFIC REQUIREMENTS WHICH
 SHALL BE MET AS WELL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  