2015-07-29 08:51:301ST REVIEW: FBC 2014 5TH ED.
  
 DENIED AS FOLLOWS:
  
 PROVIDE EVIDENCE THAT THE SOIL ENGINEER HAS REVIEWED
 THE FINAL DESIGN PER HIS REQUIREMENT ON PAGE 3 IN THE
 GEOTECHNICAL STUDY REPORT.
  
 PROVIDE ADDITIONAL DETAIL REGARDING THE ASSEMBLY AND
 WIND RESISTANCE CAPABILITY OF THE SKY PANEL SIGN. PER
 SECTION 6.0 CRITICAL FEATURES ON PAGE 17 OF 33 OF THE
 LISTING INFORMATION PROVIDED THE FIELD ASSEMBLY OF THIS
 SECTIONAL SIGN IS SUBJECT TO THE ACCEPTANCE OF THE
 LOCAL INSPECTION AUTHORITY.
  
 PROVIDE THE MANUFACTURERS INSTALLATION AND ASSEMBLY
 INSTRUCTIONS, PLEASE PROVIDE EVIDENCE THAT THE ENGINEER
 OF RECORD, CHRISTOPHER B. LAFORTE, P.E. HAS REVIEWED
 THE ASSEMBLY AND INSTALLATION INSTRUCTIONS FOR
 CONSISTENCY WITH HIS DESIGN AND THE THE SIGN PANEL HAS
 ADEQUATE WIND RESISTANCE CAPABILITY ITSELF.
  
 A DRAWING FROM ADTI MEDIA INC. WAS PROVIDED. PLEASE
 HAVE CHRISTOPHER B. LAFORTE, P.E. REVIEW NOTES 1-16 ON
 THAT DRAWING AND PROVIDE EVIDENCE OR REVIEW AND
 ACCEPTANCE OF THAT DRAWING OR ADDITIONAL DRAWINGS AND
 SPECIFICATIONS AS HE MAY REQUIRE.
  
  
 ADVISORY COMMENT:
  
 UPON INSTALLATION, A THIRD PARTY SHALL CERTIFY ALL
 BOLTED CONNECTIONS DEPICTED IN THE PLAN.
  
 A SEPARATE PERMIT IS REQUIRED FOR PLUMBING LINE
 RELOCATE AND FOR FLAG POLES RELOCATE.
  