Plan Review Notes
Plan Review Notes For Permit 15070660
Permit Number 15070660
Review Stop E
Sequence Number 2
Notes
Date Text
2015-08-26 10:59:58PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PER OUR PREVIOUS TELEPHONE CONVERSATION, MAINTAINING
 THE PATIENT BED IN EXISTING ROOM 7 WILL EXCEED THE 16
 BED LIMIT FOR MAINTAINING THE CURRENT CLASSIFICATION.
 BEING THAT THIS BED IS IN THE STAFF OFFICE, IT SHALL BE
 LABELED ACCORDINGLY OR REMOVED TO MAINTAIN THE SIXTEEN
 PATIENT BED LIMIT.
 2. THROUGH OUT YOUR ELECTRICAL NOTES YOU CONTINUE TO
 QUOTE NON APPLICABLE AND OUTDATED CODES AND SECTIONS.
 THE APPLICABLE CODES ARE: FFPC 2012 EDITION, NFPA 70
 (NEC) 2011, NFPA 72 2010 AND THE FBC-B 5TH EDITION 2014
 (MAKE A NOTE OF THIS AS THEY APPLY TO ALL FUTURE
 PERMITS)
 3. WITH THESE NEW CODES COME A CHANGE IN REQUIREMENTS
 AS WELL AS THE APPLICABLE SECTIONS. FOR EXAMPLE YOUR
 NOTE 25 WHICH REFERS TO THE LABEL OF THE OCPD IN THE
 2007 EDITION IT DOES APPEAR IN SECTION 4.4.1.4.2.2, BUT
 THIS NOW APPEARS IN SECTION 10.5.5.2.2 OF THE 2010. DO
 YOUR RESEARCH.
 4. YOU WILL HAVE TO REVIEW AND CORRECT ALL YOUR NOTES
 ACCORDINGLY.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  