| Plan Review Notes For Permit 15070660 |
| Permit Number |
15070660 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-11 13:40:19 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. THE BREAK POINT BETWEEN R4 OCCUPANCY & AN I1 | | | OCCUPANCY CLASSIFICATION REQUIRING MUCH MORE | | | RESTRICTIVE FIRE ALARM SYSTEM IS 16 BEDS. THE SUBMITTED | | | PLANS REFLECT 17 BEDS. PLEASE VERIFY AS THERE IS A | | | GREAT DIFFERENCE IN THE REQUIREMENTS. | | | 2. A MANUAL PULL STATION SHALL BE PLACED NO MORE THAN | | | 20? AND WITHIN 5 ? OF THE KITCHEN DOOR. | | | 3. A SMOKE DETECTOR IS MISSING FROM ROOM 5 | | | 4. INDICATE ON THE PLANS THE DESIGNATED OCCUPANCY | | | CLASSIFICATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | | | 2015-08-11 10:05:47 | WAITING TO SPEAK W/RICK FOR CLARIFICATION. THE BED | | | COUNT AS SUBMITTED CRATES A CHANGE IN OCCUPANCY | | | CLASSIFICATION WHICH NEED S TO BE ADDRESSED. |
|