Plan Review Notes
Plan Review Notes For Permit 15070600
Permit Number 15070600
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-08-19 10:07:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) LOCKING OF EXIT DOOR SHALL COMPLY WITH NFPA 101,
 CHAPTER 7.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 2) THE GLOW-IN-THE-DARK EXIT SIGN IS NOT APPROVED. THE
 EXIT SIGN SHALL BE HARDWAIRED WITH BATTERY BACK UP.
  