Plan Review Notes
Plan Review Notes For Permit 15070589
Permit Number 15070589
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-31 07:00:401)SUBMIT A SLAB REPAIR DETAIL FOR THE PORTION OF SLAB
 BEING REMOVED FOR THE INSTALLATION OF THE PLUMBING FOR
 THE BREAK ROOM SINK.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE DISTANCE BETWEEN THE SUPPORT LEGS FOR THE
 LAVATORIES IN THE TOILET ROOMS. A 30 INCH WIDE BY 48
 INCH LONG CLEAR FLOOR SPACE SHALL BE PROVIDED FOR A
 FORWARD APPROACH PER 5TH ED. FBC-ACCESSIBILITY
 SEC.305.3.
 3) SHOW THE DISTANCE FROM THE FINISH FLOOR TO THE
 UNDERSIDE OF THE LAVATORY VANITY. KNEE CLEARANCE SHALL
 BE PROVIDED PER 5TH ED. OF FBC-ACCESSIBILITY SEC.306.3.
 4) MIRRORS IN THE TOILET ROOMS SHALL COMPLY WITH 5TH
 ED. FBC-ACCESSIBILITY SEC.603.3.
 5) THE WALL FINISH IN THE TOILET ROOMS SHALL COMPLY
 WITH 5TH ED.FBC SEC.1210.2.2.
 6) A CLEANOUT IS REQD. IN THE BASE OF THE DRAINAGE
 STACK PER 5HT ED. OF FBC-PLUMBING SEC. 708.3.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  