| Plan Review Notes For Permit 15070589 |
| Permit Number |
15070589 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-31 07:00:40 | 1)SUBMIT A SLAB REPAIR DETAIL FOR THE PORTION OF SLAB | | | BEING REMOVED FOR THE INSTALLATION OF THE PLUMBING FOR | | | THE BREAK ROOM SINK.WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHOW THE DISTANCE BETWEEN THE SUPPORT LEGS FOR THE | | | LAVATORIES IN THE TOILET ROOMS. A 30 INCH WIDE BY 48 | | | INCH LONG CLEAR FLOOR SPACE SHALL BE PROVIDED FOR A | | | FORWARD APPROACH PER 5TH ED. FBC-ACCESSIBILITY | | | SEC.305.3. | | | 3) SHOW THE DISTANCE FROM THE FINISH FLOOR TO THE | | | UNDERSIDE OF THE LAVATORY VANITY. KNEE CLEARANCE SHALL | | | BE PROVIDED PER 5TH ED. OF FBC-ACCESSIBILITY SEC.306.3. | | | 4) MIRRORS IN THE TOILET ROOMS SHALL COMPLY WITH 5TH | | | ED. FBC-ACCESSIBILITY SEC.603.3. | | | 5) THE WALL FINISH IN THE TOILET ROOMS SHALL COMPLY | | | WITH 5TH ED.FBC SEC.1210.2.2. | | | 6) A CLEANOUT IS REQD. IN THE BASE OF THE DRAINAGE | | | STACK PER 5HT ED. OF FBC-PLUMBING SEC. 708.3.4. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|