2015-10-02 12:06:31RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- MASTER BEDROOM TRANSFER DUCT SIZE DOESN'T COMPLY
 WITH SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 ***RESPONSE:
 TRANSFER DUCT WAS CHANGED TO 12". THIS STILL DOESN'T
 COMPLY. THERE IS A 14" SUPPLY DUCT FOR THE MASTER
 BEDROOM NOT 8". REVISE AS REQUIRED.
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C FLOOR PLAN DESIGN AS REQUIRED
 BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
 NOTE: THERE ARE MANY REVISED A/C PLANS SUBMITTED ON
 DIFFERENT PAPER SIZES. PROVIDE ONLY ONE SIZE OF PLANS
 THAT CONTAINS COMPLETE FLOOR PLAN.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. SUBMIT
 OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  