| 2015-10-02 12:06:31 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- MASTER BEDROOM TRANSFER DUCT SIZE DOESN'T COMPLY | | | WITH SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION | | | (2014). | | | | | | ***RESPONSE: | | | TRANSFER DUCT WAS CHANGED TO 12". THIS STILL DOESN'T | | | COMPLY. THERE IS A 14" SUPPLY DUCT FOR THE MASTER | | | BEDROOM NOT 8". REVISE AS REQUIRED. | | | | | | 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE A/C FLOOR PLAN DESIGN AS REQUIRED | | | BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC. | | | NOTE: THERE ARE MANY REVISED A/C PLANS SUBMITTED ON | | | DIFFERENT PAPER SIZES. PROVIDE ONLY ONE SIZE OF PLANS | | | THAT CONTAINS COMPLETE FLOOR PLAN. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. SUBMIT | | | OLD COPIES FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | |
|