| Plan Review Notes For Permit 15070551 |
| Permit Number |
15070551 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-15 11:01:18 | MADE A COUPLE OF CORRECTIONS TO THE PLANS WITH NOTES | | | WRITTEN ON THE ELECTRICAL PAGE. | | | 1. CORRECTED THE REFERENCE OF "ROMEX" TO NM | | | 2.ADDED THE MISSING INTER-SYSTEM BONDING TERMINAL (NEC | | | 250.94) TO THE RISER DIAGRAM | | | 3. CORRECTED NOTE 28 TO READ 210.70 | | | CORRECTED NOTE 35 TO INCLUDE THE WEATHER RESISTANT | | | DEVICE LISTING.OF NEC 406.9(B). |
|