Plan Review Notes
Plan Review Notes For Permit 15070551
Permit Number 15070551
Review Stop E
Sequence Number 1
Notes
Date Text
2015-09-15 11:01:18MADE A COUPLE OF CORRECTIONS TO THE PLANS WITH NOTES
 WRITTEN ON THE ELECTRICAL PAGE.
 1. CORRECTED THE REFERENCE OF "ROMEX" TO NM
 2.ADDED THE MISSING INTER-SYSTEM BONDING TERMINAL (NEC
 250.94) TO THE RISER DIAGRAM
 3. CORRECTED NOTE 28 TO READ 210.70
 CORRECTED NOTE 35 TO INCLUDE THE WEATHER RESISTANT
 DEVICE LISTING.OF NEC 406.9(B).