| 2015-09-11 17:24:09 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- ENERGY CALCULATIONS: |
| | NOTE: COORDINATE THE ENERGY CALCULATIONS WITH THE FLOOR |
| | PLANS TO AVOID CONFLICTS OR DELAYS. |
| | |
| | A) PROVIDE CURRENT ENERGY CALCULATIONS FORM THAT |
| | CORRESPOND TO THE 2014 FBC. CALCULATIONS SUBMITTED ARE |
| | FOR 2010 CODE VERSION. SEC. 1106 OF FBC -EXISTING |
| | BUILDING, 5TH EDITION (2014). |
| | |
| | B) OWNER/AGENT TO CERTIFY AT THE BOTTOM OF THE FORM AS |
| | REQUIRED BY SEC. R103.1.1.2 OF FBC -EXISTING BUILDING, |
| | 5TH EDITION (2014). |
| | |
| | C) COMPLETE ALL THE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 3- SPECIFY CARBON MONOXIDE ALARMS WITHIN ALL BEDROOMS |
| | AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 4- SHEET A1.0: |
| | A) REVISE DOOR AND WINDOW NOTE: #7. SEE SEC. R612.7.2.1 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014) AND WINDOWS AND |
| | DOORS PRODUCT APPROVALS. |
| | |
| | B) REVISE WALL SCHEDULE. COORDINATE INSULATION WITH THE |
| | ENERGY CALCULATIONS. SEC. R103.2 OF FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | |
| | C) WINDOWS AND DOORS DETAILS. PROVIDE SPECIFICATIONS |
| | FOR THE 1/4" X 3" X 4" STEEL ANGLE ATTACHMENT. "ATTACH |
| | PER PRODUCT APPROVAL" IS NOT ENOUGH INFORMATION . THERE |
| | IS NOT PRODUCT APPROVAL FOR STEEL ANGLES. SEC. R301.1 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | D) PROVIDE DETAILS/SPECIFICATIONS FOR THE ATTACHMENT OF |
| | THE BRICK VENEER. SEC. R703.7 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | E) PROVIDE COMPLETE FRAMING DETAILS FOR NEW EXTERIOR |
| | WALL AT WALK-IN-CLOSET. SPECIFY ALL FRAMING FASTENERS. |
| | SEC. R301.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 5- SHEET A2.0: |
| | A) REVISE PROPOSED WEST ELEVATION. GUEST BEDROOM WINDOW |
| | IS A CASEMENT WINDOW NOT SINGLE HUNG WINDOW. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | B) REVISE PROPOSED EAST ELEVATION. THERE IS A NEW |
| | FRENCH DOOR NOT "NEW IMPACT RESISTANT WINDOW". SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 6- SHEET S2.): REVISE ENGINEERING CRITERIA. CURRENT |
| | CODE IS THE 2014 NOT 2010. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL SIMPSON |
| | STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND DETAILS. |
| | PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST THE |
| | CURRENT FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED |
| | CONNECTOR. FAC 61G20-3.002(33). |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. SUBMIT |
| | OLD COPIES FOR REFERENCE. |
| | |