2015-09-11 17:24:09RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- ENERGY CALCULATIONS:
 NOTE: COORDINATE THE ENERGY CALCULATIONS WITH THE FLOOR
 PLANS TO AVOID CONFLICTS OR DELAYS.
  
 A) PROVIDE CURRENT ENERGY CALCULATIONS FORM THAT
 CORRESPOND TO THE 2014 FBC. CALCULATIONS SUBMITTED ARE
 FOR 2010 CODE VERSION. SEC. 1106 OF FBC -EXISTING
 BUILDING, 5TH EDITION (2014).
  
 B) OWNER/AGENT TO CERTIFY AT THE BOTTOM OF THE FORM AS
 REQUIRED BY SEC. R103.1.1.2 OF FBC -EXISTING BUILDING,
 5TH EDITION (2014).
  
 C) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- SPECIFY CARBON MONOXIDE ALARMS WITHIN ALL BEDROOMS
 AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- SHEET A1.0:
 A) REVISE DOOR AND WINDOW NOTE: #7. SEE SEC. R612.7.2.1
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) AND WINDOWS AND
 DOORS PRODUCT APPROVALS.
  
 B) REVISE WALL SCHEDULE. COORDINATE INSULATION WITH THE
 ENERGY CALCULATIONS. SEC. R103.2 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 C) WINDOWS AND DOORS DETAILS. PROVIDE SPECIFICATIONS
 FOR THE 1/4" X 3" X 4" STEEL ANGLE ATTACHMENT. "ATTACH
 PER PRODUCT APPROVAL" IS NOT ENOUGH INFORMATION . THERE
 IS NOT PRODUCT APPROVAL FOR STEEL ANGLES. SEC. R301.1
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) PROVIDE DETAILS/SPECIFICATIONS FOR THE ATTACHMENT OF
 THE BRICK VENEER. SEC. R703.7 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 E) PROVIDE COMPLETE FRAMING DETAILS FOR NEW EXTERIOR
 WALL AT WALK-IN-CLOSET. SPECIFY ALL FRAMING FASTENERS.
 SEC. R301.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 5- SHEET A2.0:
 A) REVISE PROPOSED WEST ELEVATION. GUEST BEDROOM WINDOW
 IS A CASEMENT WINDOW NOT SINGLE HUNG WINDOW. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) REVISE PROPOSED EAST ELEVATION. THERE IS A NEW
 FRENCH DOOR NOT "NEW IMPACT RESISTANT WINDOW". SEC.
 107.2.1 CITY AMENDMENTS.
  
 6- SHEET S2.): REVISE ENGINEERING CRITERIA. CURRENT
 CODE IS THE 2014 NOT 2010. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL SIMPSON
 STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND DETAILS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST THE
 CURRENT FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED
 CONNECTOR. FAC 61G20-3.002(33).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. SUBMIT
 OLD COPIES FOR REFERENCE.
  