Text |
| 2015-09-21 11:17:12 | 2ND REVIEW: FBC 2014 5TH ED. |
| | |
| | APPARENTLY CHANGES WERE MADE TO THE ORIGINAL PLAN AS A |
| | FUNCTION OF THE HISTORIC REVIEW AS TO RETAINING THE |
| | CARRIAGE DOORS. THE CHANGES, ALONG WITH THE ASSOCIATED |
| | PRODUCT APPROVALS FOR THE WINDOWS AND DOORS MUST BE |
| | REVIEWED BY THE DESIGNER OF RECORD. STEPHEN GAYDOSH. |
| | (NOTE, THE RE-SUBMITTED PLAN IS NOT CONSISTENT WITH THE |
| | PREVIOUS PLAN APPROVED BY THE HISTORIC PLANNER. |
| | |
| | INDICATE IF THE BUILDING IS EXEMPT FROM THE |
| | REQUIREMENTS OF THE FBC ENERGY CONSERVATION. IF NOT, |
| | PROVIDE EITHER: |
| | |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | R303.9 REQUIRED HEATING. |
| | WHEN THE WINTER DESIGN TEMPERATURE IN TABLE R301.2(1) |
| | IS BELOW 60?F (16?C), EVERY DWELLING UNIT SHALL BE |
| | PROVIDED WITH HEATING FACILITIES CAPABLE OF MAINTAINING |
| | A MINIMUM ROOM TEMPERATURE OF 68?F (20?C) AT A POINT 3 |
| | FEET (914 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM |
| | EXTERIOR WALLS IN ALL HABITABLE ROOMS AT THE DESIGN |
| | TEMPERATURE. THE INSTALLATION OF ONE OR MORE PORTABLE |
| | SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE |
| | WITH THIS SECTION. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |