| 2015-09-03 18:32:46 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | |
| | THE CODE REFERENCE IS OUT OF DATE. THE APPLICABLE BASE |
| | CODE IS LISTED ABOVE. |
| | |
| | MODIFY THE PLAN TO DEMONSTRATE COMPLIANCE WITH THE |
| | SECTIONS LISTED BELOW: |
| | |
| | FBC 107 MINIMUM INFORMATION REQUIRED. PROVIDE A PANEL |
| | SCHEDULE, AND LIST CIRCUITS, CONDUCTOR TYPE & SIZE, AND |
| | OCP, |
| | |
| | SHOW THE METHOD OF HEATING AND AND ANY ELECTRICAL |
| | CIRCUIT FOR THIS PURPOSE. (SEE COMMENT IN BUILDING |
| | REVIEW FOR REQUIRED HEATING) IF COOLING IS TO BE |
| | PROVIDED SHOW ELECTRICAL FOR COOLING. |
| | |
| | E4002.14 TAMPER-RESISTANT RECEPTACLES. |
| | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | |
| | E3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | |
| | E3703.4 BATHROOM BRANCH CIRCUITS. |
| | A MINIMUM OF ONE 20- AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |