2015-09-03 17:30:261ST REVIEW: FBC 2014 5TH ED.
  
 THE CODE REFERENCES LISTED ON THE PLAN ARE OUT OF DATE.
 PLEASE SPECIFY THE APPROPRIATE CODE IN EFFECT AND
 INDICATE THE LEVEL OF ALTERATION OR THAT THE WORK IS A
 CHANGE OF OCCUPANCY. REVIEW OF CITY RECORDS INDICATES
 THIS IS A CHANGE OF OCCUPANCY FROM STORAGE TO
 RESIDENTIAL PER DEFINITIONIN CHAPTER 2 OF THE
 FBC-EXISTING BUILDING VOLUME 5TH EDITION.
  
 APPARENTLY CHANGES WERE MADE TO THE ORIGINAL PLAN AS A
 FUNCTION OF THE HISTORIC REVIEW AS TO RETAINING THE
 CARRIAGE DOORS. THE CHANGES, ALONG WITH THE ASSOCIATED
 PRODUCT APPROVALS FOR THE WINDOWS AND DOORS MUST BE
 REVIEWED BY THE DESIGNER OF RECORD. STEPHEN GAYDOSH.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, WINDOW, AND DOOR SUBMITTALS.
  
 INDICATE IF THE BUILDING IS EXEMPT FROM THE
 REQUIREMENTS OF THE FBC ENERGY CONSERVATION. IS THE
 BUILDING TO BE CONDITIONED SPACE? IF NOT, PROVIDE
 EITHER:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R303.9 REQUIRED HEATING.
 WHEN THE WINTER DESIGN TEMPERATURE IN TABLE R301.2(1)
 IS BELOW 60?F (16?C), EVERY DWELLING UNIT SHALL BE
 PROVIDED WITH HEATING FACILITIES CAPABLE OF MAINTAINING
 A MINIMUM ROOM TEMPERATURE OF 68?F (20?C) AT A POINT 3
 FEET (914 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM
 EXTERIOR WALLS IN ALL HABITABLE ROOMS AT THE DESIGN
 TEMPERATURE. THE INSTALLATION OF ONE OR MORE PORTABLE
 SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE
 WITH THIS SECTION.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER