| Plan Review Notes For Permit 15070532 |
| Permit Number |
15070532 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-14 19:23:13 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | | RESUBMITTED FOR A SECOND REVIEW: | | | 1. YOU SHALL SUBMIT LOAD CALCS. | | | 2. INDICATE WHICH PANEL IS BEING REPLACED AND WITH WHAT | | | IS IT BEING REPLACED. | | | 3. YOU SHALL INCLUDE THE INTER-SYSTEM BONDING TERMINAL | | | REQUIRED IN NEC250.94 | | | 4. YOU SHALL CHECK AND VERIFY THAT ALL GROUNDING IS IN | | | ACCORDANCES WITH MINIMUM CODE REQUIREMENTS. | | | 5. IF NOT ALREADY IN PLACE, PER FBC-R 314, YOU SHALL | | | COME INTO COMPLIANCE WITH SMOKE DETECTOR REQUIREMENTS. |
|