Plan Review Notes
Plan Review Notes For Permit 15070510
Permit Number 15070510
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-07-29 13:57:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. PHASE 2 - SHEET M-502 INDICATES TEMPORAY A/C
 EQUIPMENT ENCROACHING ON A REQUIRED EXIT DOOR. THE
 EQUIPMENT SHALL NOT IMPEDE OCCUPANT EGRESS. EQUIPMENT
 SHALL BE MOVE AWAY FROM THE EXIT OPENING.
  
 2. PHASE 3 - SHEET M-501 INDICATES TEMPORAY A/C
 EQUIPMENT POSSIBLY ENCROACHING ON A REQUIRED EXIT DOOR.
 THE EQUIPMENT SHALL NOT IMPEDE OCCUPANT EGRESS.
 EQUIPMENT SHALL BE MOVE AWAY FROM THE EXIT OPENING.
  
  
  
  