| Plan Review Notes For Permit 15070501 |
| Permit Number |
15070501 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-23 11:25:23 | 1ST REVIEW: FBC 2014 MECHANICAL | | | | | | 1) PLEASE REMOVE THE AC CHANGE OUT FORM FROM THE PERMIT | | | SUBMITTAL PACKAGE: THIS IS NOT A CHANGE OUT, IT IS A | | | NEW INSTALLATION. | | | 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN | | | INDICATING THE MAKE AND MODEL NUMBERS OF THE CONDENSER | | | AND THE AIR HANDLER, COOLING AND HEATING CAPACITIES, | | | EFFICIENCY RATING, AND ELECTRICAL DATA. | | | 3) CLARIFY THE SCOPE OF THE PROJECT WITH NOTES ON THE | | | PLANS. INDICATE IF THE SYSTEM IS SUPPLEMENTAL TO A MAIN | | | SYSTEM AND IDENTIFY THE ROOM IT IS CONDITIONING- | | | BEDROOM, DEN, ENCLOSED PORCH? | | | 4) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | | CONDENSER PAD, AND WIND LOAD TIE DOWN ENGINNERING FOR | | | THE CONDENSER PER MANUFACTURER'S SPECIFICATIONS- REFER | | | TO SECTION M1401.4 FBC-10 RESIDENTIAL. | | | 5) PROVIDE AN ELECTRICAL PLAN AND AN ELECTRICAL | | | SUB-PERMIT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|