| Plan Review Notes For Permit 15070489 |
| Permit Number |
15070489 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-09-10 21:07:31 | PREVIOUS NOTE 7 - THE ELECTRICAL DATUM PLANE AND | | | DISCONNECTING REQUIREMNENTS ARE A FAIRLY NEW | | | REQUIREMENT IN THE ELECTRICAL CODE AND NOT PREVIOUSLY | | | ADDRESSED. PROVIDE AN ACTUAL ELEVATION FOR THE | | | ELECTRICAL DATUM PLANE AND SHOW COMPLIANCE WITH THE NEC | | | REQUIREMENTS. | | | PREVIOUS NOTE 9 - IF THE ELECTRICAL DATUM PLANE IS NOT | | | SHOWN AND ESTABLISHED, THE PLANS ARE NOT IN COMPLIANCE | | | WITH THE GOVERNING ELECTRICAL REQUIREMENTS. COMPLETE | | | REVIEW SHOULD REVEAL OTHER NON-COMPLIANT ITEMS. | | | PREVIOUS NOTE 16 - PROVIDE INFORMATION TO THE FIELD | | | INSPECTOR AT THE TIME OF THE INSPECTION SHOWING THE | | | COMPATIBILITY AND LISTING INFORMATION OF THE COMPONENTS | | | TO BE CONNECTED FOR SUITABILITY OF USE. |
|