| 2015-08-20 14:51:09 | |
| | 17 PEDESTALS CALLED OUT ON TABLE, ONLY 10 INDICATED ON |
| | PLAN, RISER INDICATES 16 SETS OF CONDUCTORS |
| | PROVIDE COPY OF FPL METERED LOADS FOR FILE TO JUSTIFY |
| | LOAD CALCULATIONS |
| | PLEASE EXPLAIN THE FEEDER SCHEDULE - QUANTITY OF PHASE |
| | CONDUCTORS, SIZE OF GROUNDED AND GROUNDING CONDUCTORS |
| | IF PHASE CONDUCTORS ARE INCREASED FOR VOLTAGE DROP, EGC |
| | MUST BE RESIZED ACCORDINGLY |
| | PROVIDE VOLTAGE DROP CALCULATIONS |
| | PLANS CALL FOR 2008 NEC, THE CURRENT EDITION IS THE |
| | 2011 NEC |
| | CORRECT EDITION OF THE FLORIDA BUILDING CODE IS THE 5TH |
| | EDITION |
| | PROVIDE TOPOGRAPHIC INFORMATION FOR ELECTRICAL DATUM |
| | PLANE AND AND COMPLIANCE WITH 555.2 AND 555.9. OTHER |
| | SECTIONS AS APPLICABLE |
| | PROVIDE LOAD CALCULATION SHOWING CONFORMANCE WITH |
| | 555.12 |
| | ENSURE INSTALLATION IS IN COMPLIANCE WITH NEC ARTICLE |
| | 555 |
| | PROVIDE SPECIFICATIONS AND LISTING INFORMATION ON |
| | PEDESTALS. INVESTIGATED MANUFACTURERS SITE AND COULD |
| | NOT LOCATE LISTING INFO |
| | THE NUMBER OF PEDESTALS IN THE TABLE, SHOWN ON THE SITE |
| | PLAN AND IN THE ONE LINE DIAGRAM DOES NOT APPEAR TO |
| | MATCH. WHAT WAS USED FOR THE LOAD CALCULATION? |
| | HOW WAS THE KW FOR RECEPTACLES IN THE LOAD CALCULATION |
| | DETERMINED? |
| | IS NOTE 1 TO TABLE 555.12 BEING UTILIZED? |
| | INDICATE PROVISION OF GFP PER 555.3 |
| | PROVIDE CALCULATIONS OR CONFORMATION OF VOLTAGE DROP |
| | COMPLIANCE WITH FLORIDA BUILDING CODE - ENERGY |
| | CONSERVATION AND NECA STANDARDS OF INSTALLATION |
| | PROVIDE LISTING OR INTENT FOR FIELD EVALUATION OF |
| | EQUPMENT THAT WILL BE FIELD MODIFIED (SUCH AS MSB #4) |
| | 110.3 |
| | PROVIDE ARC FLASH PROTECTION PER NEC 110 |