2015-07-13 15:04:541ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15070454, MASTER #14090842
  
 1) THE REVISED AC PLANS INDICATE AN INCREASE IN COOLING
 CAPACITY FOR AC #3- FROM 3.5 TONS TO 5 TONS. PROVIDE AC
 LOAD CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL N OR
 ASHRAE/ACCA STANDARD 183- REFERENCE SECTION 503.2.1
 FBC-10 ENERGY CONSERVATION.
 2) THE REVISED PLAN DOES NOT SHOW ANY CONDTIONING FOR
 THE 2ND FLOOR STORAGE ROOMS IN THE SE CORNER OF THE
 BUILDING. THE ORIGINAL PLANS SHOWED SUPPLY AND RETURN
 AIR IN THESE ROOMS: PLEASE CLARIFY WHY THE CONDITIONING
 IS BEING REMOVED.
 3) PROVIDE AHRI CERTIFICATES FOR THE NEW SYSTEMS-
 SECTION 101.4.7 FBC-10 ENERGY CONSERVATION.
 4) REVISE THE ELECTRICAL PLANS TO SHOW THE CORRECT WIRE
 AND BREAKER SIZES FROR AHU-3