| Plan Review Notes For Permit 15070454 |
| Permit Number |
15070454 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-13 15:04:54 | 1ST REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15070454, MASTER #14090842 | | | | | | 1) THE REVISED AC PLANS INDICATE AN INCREASE IN COOLING | | | CAPACITY FOR AC #3- FROM 3.5 TONS TO 5 TONS. PROVIDE AC | | | LOAD CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL N OR | | | ASHRAE/ACCA STANDARD 183- REFERENCE SECTION 503.2.1 | | | FBC-10 ENERGY CONSERVATION. | | | 2) THE REVISED PLAN DOES NOT SHOW ANY CONDTIONING FOR | | | THE 2ND FLOOR STORAGE ROOMS IN THE SE CORNER OF THE | | | BUILDING. THE ORIGINAL PLANS SHOWED SUPPLY AND RETURN | | | AIR IN THESE ROOMS: PLEASE CLARIFY WHY THE CONDITIONING | | | IS BEING REMOVED. | | | 3) PROVIDE AHRI CERTIFICATES FOR THE NEW SYSTEMS- | | | SECTION 101.4.7 FBC-10 ENERGY CONSERVATION. | | | 4) REVISE THE ELECTRICAL PLANS TO SHOW THE CORRECT WIRE | | | AND BREAKER SIZES FROR AHU-3 |
|