| 2015-09-02 10:15:24 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. YOU SHALL SUBMIT A DATA SHEET FOR THE UNIMODE 600 |
| | ANN. ( I TRIED TO GET THIS FOR YOU BUT WAS UNABLE TO) |
| | 2. SMOKE DETECTOR IN MANAGER'S APARTMENT LIVING ROOM |
| | SHALL BE RELOCATED CLOSER TO THE BEDROOM, MAKE SURE TO |
| | STAY 3' FROM BATHROOM DOOR AND 10' FROM RANGE. |
| | 3. LEVEL 2, UNIT 1 BEDROOM 2 MISSING S/D OUTSIDE OF |
| | DOOR. WHAT IS THAT WIC EXITING TO CORRIDOR? IF EXIT TO |
| | CORRIDOR WILL NEED A S/D AS WELL. |
| | 4. LEVEL 2, UNIT 3 BEDROOM 2 MISSING S/D AS WELL. |
| | 5. LEVELS 3 THROUGH LEVEL 7 ARE MISSING THE HEAT |
| | DETECTOR UNIT FROM THE LEGEND AS WELL AS THE TYPICAL |
| | MISSING S/D AS INDICATED ABOVE. |
| | 6. LEVEL 8 UNITS 1 & UNIT 2 MISSING S/D FOR BEDROOM 2. |
| | 7. MAY HAVE TO ADJUST LIVING ROOM S/D WITH RELATION TO |
| | THE BEDROOM DOOR. |
| | 8. RISER AND CALCULATIONS MAY VARY DEPENDING ON HOW THE |
| | ABOVE CORRECTIONS ARE ADDRESSED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |