| 2015-07-15 17:49:50 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. THE FIRST FLOOR BEDROOM ON THE EAST END IS MISSING |
| | THE NOTIFICATION APPLIANCE. |
| | 2. THAT SAME BEDROOM IS MISSING THE SMOKE DETECTOR |
| | REQUIRED ON THE OUTSIDE OF THE ROOM. |
| | 3. ELEVATOR LOBBY MISSING RECALL DETECTOR. |
| | 4. THE N.E. PARKING AREA MISSING NOTIFICATION |
| | APPLIANCE. |
| | 5. TYPICAL TO FLRS. 2 ? 6 & 8: |
| | A) MISSING SMOKE DETECTOR IN ELEVATOR LOBBIES. |
| | B) SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN A |
| | RADIUS OF 10? FROM A COOKING APPLIANCE UNLESS |
| | SPECIFICALLY LISTED FOR THE PURPOSE. |
| | 6. FLOOR PLAN FOR LEVEL 7 VARIES FROM THE REST; ROOMS |
| | SHALL BE LABELED FOR IDENTIFICATION. |
| | 7. FLOOR 9 VARIES AS WELL, ALL ROOMS SHALL BE |
| | IDENTIFIED. |
| | 8. BECAUSE THE DEVICE COUNT WILL VARY, THE RISER AND |
| | CALCS SHALL BE REVISED ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |