| Plan Review Notes For Permit 15070440 |
| Permit Number |
15070440 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-01 13:39:18 | 2ND REVIEW: FBC 2014 5TH ED. | | | | | | YOU HAVE NOW SUBMITTED IN ADDITION TO THE SPEC SHEET | | | FOR APC CORK, A PLUMBING RISER AND A STATEMENT THAT YOU | | | ARE CONVERTING A TUB TO A SHOWER AND KITCHEN CABINET | | | DRAWINGS FROM HOME DEPOT. | | | | | | YOU SUBMITTED NO TEST REPORTS ON THE STC AND ICC FOR | | | THE CORK AND YOU DID NOT PROVIDE THE FLOOR ASSEMBLY . | | | THE REPORT WE HAVE ON FILE FOR THIS PRODUCT IS FOR USE | | | WITH QUARRY TILE OVER A 6" CONCRETE SLAB. ARE YOU USING | | | QUARRY TILE? WHAT IS THE THICKNESS OF THE SLAB? PLEASE | | | PROVIDE TEST REPORTS AND A BETTER PLAN TO INDICATE WHAT | | | THE MATERIALS ARE TO BE FOR THE BATHROOM | | | RE-CONFIGURATION. IT MAY BE THAT THIS CORK PRODUCT DOES | | | NOT MEET THE SOUND TRANSMISSION CRITERIA OF FBC 1207. | | | | | | PLEASE PROVIDE A PLAN AS REQUESTED PRIOR PER FBC | | | 107.2.1 TO FULLY INDICATE THE EXTENT OF THE WORK | | | PROPOSED IN DETAIL. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|