Plan Review Notes
Plan Review Notes For Permit 15070429
Permit Number 15070429
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-14 08:40:301ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070429
 7/14/15
  
 1) THE FLORIDA BUILDING CODES 5TH EDITION 2014 WENT
 INTO EFFECT ON JUNE 30, 2015. PLEASE REVIEW AND UPDATE
 THE DESIGN CRITERIA LISTED UNDER PROJECT INFORMATION ON
 SHEET A0.1.
 2) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL N OR
 THE ACCA/ASHRAE STANDARD 183- SECTION C403.2.1 FBC-2014
 ENERGY CONSERVATION.
 3) THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING
 CONDITIONED MUST BE BROUGHT INTO FULL COMPLIANCE WITH
 THE FBC-2014 ENERGY CONSERVATION CODE- SEE SECTION
 C101.4.5. PLEASE SUBMIT TWO COPIES OF FORM C402 FOUND
 IN APPENDIX C OF THE CODE BOOK, OR A COMPLIANCE
 CERTIFICATION DOCUMENT FROM FLORIDA BUILDING COMMISSION
 APPROVED SOFTWARE.
 4) THE RTU TIE DOWN DETAILS ARE INCOMPLETE: INDICATE
 THE TYPE, SIZE, AND SPACINGS OF FASTENERS TO BE USED TO
 MOUNT THE RTU'S TO THE CURBS- REFERENCE SECTION 301.15
 FBC-14 MECHANICAL FOR ADDITIONAL COMPLIANCE CRITERIA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER