| 2015-07-14 08:40:30 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15070429 | | | 7/14/15 | | | | | | 1) THE FLORIDA BUILDING CODES 5TH EDITION 2014 WENT | | | INTO EFFECT ON JUNE 30, 2015. PLEASE REVIEW AND UPDATE | | | THE DESIGN CRITERIA LISTED UNDER PROJECT INFORMATION ON | | | SHEET A0.1. | | | 2) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR | | | THE NEW AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL N OR | | | THE ACCA/ASHRAE STANDARD 183- SECTION C403.2.1 FBC-2014 | | | ENERGY CONSERVATION. | | | 3) THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING | | | CONDITIONED MUST BE BROUGHT INTO FULL COMPLIANCE WITH | | | THE FBC-2014 ENERGY CONSERVATION CODE- SEE SECTION | | | C101.4.5. PLEASE SUBMIT TWO COPIES OF FORM C402 FOUND | | | IN APPENDIX C OF THE CODE BOOK, OR A COMPLIANCE | | | CERTIFICATION DOCUMENT FROM FLORIDA BUILDING COMMISSION | | | APPROVED SOFTWARE. | | | 4) THE RTU TIE DOWN DETAILS ARE INCOMPLETE: INDICATE | | | THE TYPE, SIZE, AND SPACINGS OF FASTENERS TO BE USED TO | | | MOUNT THE RTU'S TO THE CURBS- REFERENCE SECTION 301.15 | | | FBC-14 MECHANICAL FOR ADDITIONAL COMPLIANCE CRITERIA. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|