| 2015-10-05 18:33:39 | THIRD CHECKLIST TO REVISION TO ADDRESS BUILDING |
| | PROVISO: |
| | |
| | 1- PROVIDE COMPLETE DETAILS & SPECIFICATIONS FOR THE |
| | OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND |
| | OFFICE. SEC. R302.5. |
| | |
| | RESPONSE : SIZE OF WINDOW SPECIFIED ON SHEET A-1 |
| | EXCEEDS THE SIZE SHOWN ON INFORMATION SUBMITTED. REVISE |
| | SPECIFICATIONS ON SHEET A-1 AS REQUIRED. |
| | NOTE: MANUFACTURER SPECIFICATIONS SUBMITTED TO BE |
| | APPROVED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL TO |
| | THIS OFFICE. SEC. 107.3.4.2 CITY AMENDMENTS. |
| | |
| | 2- ENTRY DOOR PRODUCT APPROVALS ASSEMBLY SUBMITTED: |
| | MULLION FLORIDA PRODUCT APPROVAL FL17472-R1 WAS |
| | ALTERED. THE DESIGN PRESSURES TABLES ON SHEET 6 OF 11 |
| | THRU 10 OF 11 WERE REMOVED FROM THE DRAWINGS SUBMITTED. |
| | THIS IS NOT ACCEPTABLE. THE DESIGN PRESSURE TABLES ARE |
| | ESSENTIAL TO DETERMINE IF THE SELECTED MULLION SIZE |
| | WILL RESIST THE CALCULATED DESIGN PRESSURES. PROVIDE |
| | UN-ALTERED PRODUCT APPROVAL AND CLEARLY MARK MULLION |
| | SIZE TO BE USED ON THE ENTRY DOOR ASSEMBLY. SEC. R301 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- EXTERIOR DOOR SCHEDULE WAS REVISED. DOORS NUMBERS 1, |
| | 3, 4 AND 5 WERE REVISED TO 8'-1" HIGH DOORS. PROVIDE |
| | PRODUCT APPROVALS FOR ALL DOORS THAT COVERS THAT SIZE |
| | OR REVISE DOOR SCHEDULE AS REQUIRED. FAC |
| | 61G20-3.002(33). |
| | NOTE: DOORS WERE 8'-0" HIGH ON APPROVED PLANS. |
| | |
| | 4- OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE |
| | PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4. SEE ITEM |
| | #3 ABOVE. |
| | |
| | 5- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |