Date Text
2015-07-30 14:54:55 
 7/30/15 FIRST REVIEW DENIED
  
  
 COMMENTS
 1.MIDDLE WATER CLOSET IN WOMANS BATHROOM MUST TIE INTO
 HORIZONTAL WET VENT BETWEEN OTHER TWO TOILETS.
 FBCP 912.1
  
 2.WASHING MACHINE MUST TIE INTO BUILDING DRAIN DOWN
 STREAM OF LAST FIXTURE IN BATHROOM GROUP.
 FBC 912.1
  
 3. NEW WATER CLOSET IN MENS BATHROOM MUST BE
 INDUVIDUALY VENTTED THIS IS NOT A CIRCUIT VENT.
 FBCP914.1
  
  
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL