| 2015-07-23 10:27:28 | 4920 LORING DRIVE - CONSTRUCTION TRAILERS |
| | PERMIT #15070309 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVISO - SUBMIT REVISION ADDRESSING PLAN REVIEW |
| | COMMENTS |
| | |
| | **A #131 FIRE FINAL INSPECTION IS NEEDED BEFORE |
| | OCCUPANCY OF THE STRUCTURE IS PERMITTED** |
| | |
| | DRAWING A1 INDICATES A "DOUBLE-WIDE" TRAILER STRUCTURE |
| | WITH DIMENSIONS OF 44' X 23' (1,012 SQ.FT.); HOWEVER, |
| | SITE PLAN DRAWING SP1 INDICATES A STRUCTURE AREA OF |
| | 3,278 SQ.FT. PROVIDE AN ACCURATE PLAN SHOWING THE |
| | CONFIGURATIONS AND LOCATIONS OF THE TRAILERS. |
| | |
| | NO PLANS SUBMITTED FOR STAIRS, HANDRAILS OR GUARDRAILS. |
| | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. |
| | HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND |
| | NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, |
| | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| | LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE |
| | RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| | 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE |
| | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, |
| | MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. |
| | OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH |
| | DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE |
| | TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND |
| | BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE |
| | PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL |
| | BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS |
| | SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH |
| | OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | NOTE: CIVIL DRAWING 1 OF 2 INDICATES THE INSTALLATION |
| | OF A NEW FIRE HYDRANT AND NEW UNDERGROUND FIRE MAIN. A |
| | SEPARATE PLAN AND PERMIT (UG FIRELINE) IS REQUIRED FOR |
| | THIS WORK. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |