| Plan Review Notes For Permit 15070309 |
| Permit Number |
15070309 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-02 20:06:13 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. PROVIDE DETAIL AS TO THE CONNECTION OF EACH TRAILER. | | | 2. PROVIDE GROUNDING DETAIL FOR THE TRAILERS AS WELL AS | | | THE SUPPORT POLES. | | | 3. THOUGH THE TRAILER IS A PREASSEMBLED UNIT, ALREADY | | | INSPECTED AT THE MANUFACTURER, I NEED TO KNOW WHAT ARE | | | THE ELECTRICAL REQUIREMENTS/LOAD DEMAND FOR EACH UNIT | | | 4. UPDATE THE APPLICABLE CODES: NEC 2011 & FBC 5TH | | | EDITION | | | 5. CORRECT NOTES D-3 AS IT IS CONTRADICTORY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|