| Plan Review Notes For Permit 15070286 |
| Permit Number |
15070286 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-10 10:46:00 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRIC | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS, INSTALLATION INSTRUCTIONS AND LISTING | | | FOR THE ELECTRIC POOL HEATER. FBC 107.2.1 | | | | | | 2) SUBMIT ELECTRIC LOAD CALCULATIONS AND PANEL SCHEDULE | | | SHOWING THAT THE EXISTING SERVICE IS CAPABLE OF | | | ACCOMMODATING THE ADDITIONAL LOADS. NEC 220.16(2) | | | |
|