| Plan Review Notes For Permit 15070276 |
| Permit Number |
15070276 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-08-17 12:31:22 | GAS REVIEW - THE FOLLOWING DEFICIENCIES HAVE BEEN | | | NOTED: | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | TANKLESS GAS WATER HEATER. THE APPLIANCE SHALL BE | | | LISTED AND LABELED PER 2014 FBC-R SEC. G 2404.3. | | | 2) INDICATE THE DELIVERY PRESSURE OF THE GAS SYSTEM. | | | 2014 FBC-R SEC.G2413.2. | | | 3) INDICATE THE TYPE OF PIPING TO BE INSTALLED IN THE | | | CEILING TO THE RANGE AND THE DRYER.WPB AMEND. TO FBC | | | SEC. 107.3.5.3. | | | 4) SUBMIT COMBUSTION AIR CALCCULATIONS FOR THE RANGE | | | AND DRYER. 2014 FBC-R SEC.G2407. | | | 5) IF THIS IS A 1/2 LB PRESSURE SYSTEM, THE SYSTEM IS | | | UNDERSIZED.THE APPLICABLE TABLE IS G2413.4 (1) AND THE | | | LENGTH COLUMN TO BE USED FOR SIZING THE SYSTEM IS 40 | | | FEET.THE MAXIMUM BTU LOAD ON A 1" PIPE IS 320,000. THE | | | MINIMUM SIZE FROM THE METER SHALL BE 1 1/4 INCHES | | | (SEC.A) , THE SIZE TO THE TANKLESS WATER HEATER SHALL | | | BE 1" (SEC. B) AND THE LINE SUPPLYING THE RANGE AND | | | HEATER SHALL BE 3/4"(SEC.C). | | | | | | A NOTE CAN BE PLACED ON THE PLAN STATING THAT THE GAS | | | WILL BE UNDER A SEPARATE PERMIT AND THE GAS DRAWING | | | SHALL BE REMOVED FROM THE PLANS AND THEN I CAN APPROVE | | | IT AS A SEPARATE PERMIT REQUIRED PROVISO. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|