| Plan Review Notes For Permit 15070276 |
| Permit Number |
15070276 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-08 03:57:24 | GAS SHALL BE UNDER A SEPARATE PERMIT. THE FOLLOWING | | | ITEMS NEED TO BE ADDRESSED WHEN THE GAS PERMIT | | | APPLICATION IS SUBMITTED. | | | | | | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED | | | PER 20114 FBC -RESIDENTIAL SEC.G2404.3. | | | 2) INDICATE THE DELIVERY PSI OF THE GAS FOR THE SYSTEM. | | | 3) INDICATE THE APPLICABLE SIZING TABLES FROM CHAPTER | | | 24 OF THE 2014 FBC - RESIDENTIAL USED TO SIZE THE | | | SYSTEM. | | | 4) INDICATE ON THE PLAN THE TYPE OF PIPE MATERIAL USED | | | INSIDE THE STRUCTURE. | | | 5) THE SIZE OF THE GAS SUPPLY FROM THE METER MAY BE | | | UNDERSIZED BASED ON THE BTU LOAD & THE TOTAL DISTANCE | | | TO THE MOST REMOTE OUTLET. THIS WILL BE DETERMINED WHEN | | | THE ADDITIONAL REQUESTED INFORMATION IS SUBMITTED. THE | | | LINE MAY HAVE TO BE INCREASED TO 1 1/2 INCHES.THE | | | ENTIRE SYSTEM MAY BE UNDERSIZED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|