Plan Review Notes
Plan Review Notes For Permit 15070263
Permit Number 15070263
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-12 09:02:001ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070263
 8/12/15
  
 1) REFERENCE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: PROVIDE COOLING AND HEATING LOAD
 CALCULATIONS FOR THE NEW OFFICE AC SYSTEM IN ACCORDANCE
 WITH ACCA MANUAL N OR THE ACCA/ASHRAE STANDARD 183.
 2) SHEET M-1, KEYNOTE #1: REFERENCE SECTION 306.1
 FBC-14 MECHANICAL AND REVISE THE NOTE TO SHOW
 COMPLIANCE.
 306.1 ACCESS FOR MAINTENANCE AND REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT DISABLING THE FUNCTION
 OF A FIRE-RESISTANCE-RATED ASSEMBLY OR REMOVING
 PERMANENT CONSTRUCTION, OTHER APPLIANCES, VENTING
 SYSTEMS OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO
 THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED OR
 REPLACED. A LEVEL WORKING SPACE AT LEAST 30 INCHES DEEP
 AND 30 INCHES WIDE (762 MM BY 762 MM) SHALL BE PROVIDED
 IN FRONT OF THE CONTROL SIDE TO SERVICE AN APPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  