2015-07-09 15:59:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A-3.0, DOOR SCHEDULE, DOORS R & E LOCATED AT
 THE SPACE INDICATED ON SHEET A-1.0 AS NEW CORRIDOR,
 DOES NOT INDICATE THE DOOR HARDWARE AND LOCKING OR
 LATCHING.
  
 2) SHEET A-0.0 INDICATES EXIT PASSAGE THRU A ROOM
 INDICATED ON SHEET A-1.0 AS NEW CORRIDOR. ACCESS TO AN
 EXIT SHALL NOT PASS THROUGH KITCHENS, STOREROOMS,
 RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS, OR OTHER
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SBJECT TO
 LOCKING UNLESS PERMITTED BY THE OCCUPANCY CHAPTER.
 CHAPTER 39, EXISTING BUSINESS OCCUPANCIES, DOES NOT
 ALLOW FOR PASSAGE THROUGH THIS ROOM.
 THE EXIT SHALL NOT PASS THROUGH THIS ROOM AS
 CONFIGURED.