| 2015-07-09 15:59:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET A-3.0, DOOR SCHEDULE, DOORS R & E LOCATED AT | | | THE SPACE INDICATED ON SHEET A-1.0 AS NEW CORRIDOR, | | | DOES NOT INDICATE THE DOOR HARDWARE AND LOCKING OR | | | LATCHING. | | | | | | 2) SHEET A-0.0 INDICATES EXIT PASSAGE THRU A ROOM | | | INDICATED ON SHEET A-1.0 AS NEW CORRIDOR. ACCESS TO AN | | | EXIT SHALL NOT PASS THROUGH KITCHENS, STOREROOMS, | | | RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS, OR OTHER | | | SIMILAR SPACES, OR OTHER ROOMS OR SPACES SBJECT TO | | | LOCKING UNLESS PERMITTED BY THE OCCUPANCY CHAPTER. | | | CHAPTER 39, EXISTING BUSINESS OCCUPANCIES, DOES NOT | | | ALLOW FOR PASSAGE THROUGH THIS ROOM. | | | THE EXIT SHALL NOT PASS THROUGH THIS ROOM AS | | | CONFIGURED. |
|