| 2015-07-22 16:21:50 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15070263 |
| | ADD: 2580 METROCENTRE BLVD. SUITE # 3B |
| | CONT: EMERALD CONSTRUCTION |
| | TEL: (954)241-2583 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 22/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A-0.0 INDICATES THE PLANS WERE |
| | DESIGNED TO THE 2010 FBC. PLEASE BE AWARE THAT THE 2014 |
| | FBC WAS ADOPTED STATE WIDE JUNE 30/ 2015. |
| | PLANS WILL NEED TO BE UPDATED TO THE CURRENT ADOPTED |
| | CODE. |
| | |
| | 2) SHEET A-1.0: |
| | 1A) THE NEW DOOR IN THE OLD TENANT SEPARATION WALL IS |
| | ONLY IDENTIFIED AS R SHEET A-3.0 INDICATES THIS DOOR TO |
| | BE RE-USED BUT NO DOOR SIZE IS GIVEN. PLEASE PROVIDE |
| | CODE COMPLIANCE WITH THE 2014 FBC-B 1008.1.1 SIZE OF |
| | DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE |
| | SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL |
| | PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR |
| | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 1B) SHEET A-1.0 DOOR IS A NEW DOOR LOCATION, A NEW |
| | DOOR, THE DOOR SCHEDULE ON A-3.0 INDICATES THIS DOOR TO |
| | BE A 2'-6" DOOR. PLEASE PROVIDE CODE COMPLIANCE WITH |
| | THE 2014 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM |
| | WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE |
| | OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH |
| | OF 32 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH |
| | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 2) COVERSHEET AT THE TOP OF THE SHEET THE MEANS OF |
| | EGRESS GOES THROUGH WHAT APPEARS TO BE A BREAK ROOM. |
| | NONE OF THE SHEETS LABEL THE USE OF THIS ROOM, FBC-B |
| | ALLOWS FOR EGRESS THROUGH INTERVENING ROOM THIS ROOM |
| | APPEARS TO BE A BREAK ROOM. THE CODE WILL NOT ALLOW A |
| | MEANS OF EGRESS THROUGH A KITCHEN, PLEASE LABEL THE USE |
| | OF THIS SPACE. |
| | |
| | 3) IT APPEARS ON M-1.0 THERE WILL BE A NEW EXTERIOR |
| | WALL LOUVER FOR OUTSIDE AIR. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (3)(C) WALL LOUVERS |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |