Plan Review Notes
Plan Review Notes For Permit 15070263
Permit Number 15070263
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-22 16:21:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070263
 ADD: 2580 METROCENTRE BLVD. SUITE # 3B
 CONT: EMERALD CONSTRUCTION
 TEL: (954)241-2583
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 22/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET A-0.0 INDICATES THE PLANS WERE
 DESIGNED TO THE 2010 FBC. PLEASE BE AWARE THAT THE 2014
 FBC WAS ADOPTED STATE WIDE JUNE 30/ 2015.
 PLANS WILL NEED TO BE UPDATED TO THE CURRENT ADOPTED
 CODE.
  
 2) SHEET A-1.0:
 1A) THE NEW DOOR IN THE OLD TENANT SEPARATION WALL IS
 ONLY IDENTIFIED AS R SHEET A-3.0 INDICATES THIS DOOR TO
 BE RE-USED BUT NO DOOR SIZE IS GIVEN. PLEASE PROVIDE
 CODE COMPLIANCE WITH THE 2014 FBC-B 1008.1.1 SIZE OF
 DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 1B) SHEET A-1.0 DOOR IS A NEW DOOR LOCATION, A NEW
 DOOR, THE DOOR SCHEDULE ON A-3.0 INDICATES THIS DOOR TO
 BE A 2'-6" DOOR. PLEASE PROVIDE CODE COMPLIANCE WITH
 THE 2014 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM
 WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH
 OF 32 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 2) COVERSHEET AT THE TOP OF THE SHEET THE MEANS OF
 EGRESS GOES THROUGH WHAT APPEARS TO BE A BREAK ROOM.
 NONE OF THE SHEETS LABEL THE USE OF THIS ROOM, FBC-B
 ALLOWS FOR EGRESS THROUGH INTERVENING ROOM THIS ROOM
 APPEARS TO BE A BREAK ROOM. THE CODE WILL NOT ALLOW A
 MEANS OF EGRESS THROUGH A KITCHEN, PLEASE LABEL THE USE
 OF THIS SPACE.
  
 3) IT APPEARS ON M-1.0 THERE WILL BE A NEW EXTERIOR
 WALL LOUVER FOR OUTSIDE AIR.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (3)(C) WALL LOUVERS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  