| Plan Review Notes For Permit 15070224 |
| Permit Number |
15070224 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-17 14:16:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE USE OF THE ROOM IS NOT CLEAR. PLAN STATES THIS | | | IS A "REPUMP ROOM." A FIRE RATED DOOR WITH A CLOSER IS | | | PROPOSED. | | | | | | SEE FBC 1008.1.10: | | | | | | ELECTRICAL ROOMS WITH EQUI9PMENT RATED 1200 AMPERES OR | | | MORE AND OVER 6 FEET WIDE THAT CONTAIN OVER-CURRENT | | | DEVICES, SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT | | | OR EXIT ACCESS DOORS SHALL BE EQUIPPED WITH PANIC | | | HARDWARE OR FIRE EXIT HARDWARE. | | | | | | REVISE PLAN TO SHOW COMPLIANCE. | | | | | | 2. ON THE PLAN, PROVIDE THE PRINTED NAME AND SIGNATURE | | | OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE PLAN, | | | FBC 107. | | | | | | |
|