 PROJECT: LOFTIN PLACE SITE LIGHTING
 PERMIT#: 15070211
 CODE: 2011 EDITION OF THE NEC, 5TH EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PAGE E-3 CLARIFY A DESIGN CONFLICT OF EXISTING
 ELECTRICAL SERVICE POINT B (OLIVE) THE TOP DESIGN OF
 THE RACK INDICATES A 300AMP MB WITH THREE CONTCTORS.
 THE DESIGN AT THE BOTTOM OF THE PAGE INDICATES A 200AMP
 FUSED DISCONNECT. AND THE PANEL SCHEDULE FOR PANEL B
 INDICATES A 200AMP MLO.
 PLEASE CLARIFY WHICH DESIGN IS ACURATE? 300AMP? OR
 200AMP? MAIN BREAKER OR MAIL LUG ONLY?LASTLY IS THERE
 ONE CONTACTOR CONTROLING THE WHOLE PANEL OR ARE THERE
 THREE CONTACTORS CONTROLLING THE BRANCH CIRCUITS?
  
 2) PROVIDE LEGIBLE LIGHTING FIXTURE SCHEDULE AND LOAD
 CALCULATION SUMMARY.
  
 3) INDICATE COMPLIANCE WITH THE FBC-ENERGY 505.2
  
 4) PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES
 INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  